conduit fill chart for rigid pvc conduit

Back to References Menu

PVC Conduit Fill Table (THWN, THHN Wire)


This PVC conduit fill table is used to determine how many THWN or THHN wires can be safely put into PVC conduit tubing. Each row going across is a different size of PVC conduit (Schedule 40 or 80). Each column (going up and down) is a different gauge of wire. The results show the allowable number of wires for each size/type of conduit and wire, based on the 2020 NEC code.

Conduit
Trade Size
in Inches

Wire Conductor Size (THWN, THHN)

AWG MCM (kcmil)
14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900
1⁄2 1/2 Inch Schedule 40 11 8 5 3 1 1 1 1 1 1
1/2 Inch Schedule 80 9 6 4 2 1 1 1 1
3⁄4 3/4 Inch Schedule 40 21 15 9 5 4 2 1 1 1 1 1 1 1
3/4 Inch Schedule 80 17 12 7 4 3 1 1 1 1 1 1 1
1 1 Inch Schedule 40 34 25 15 9 6 4 3 3 1 1 1 1 1 1 1 1
1 Inch Schedule 80 28 20 13 7 5 3 3 2 1 1 1 1 1 1
1 1⁄4 1 1/4 Inch Schedule 40 60 43 27 16 11 7 6 5 3 3 2 1 1 1 1 1 1 1 1
1 1/4 Inch Schedule 80 51 37 23 13 9 6 5 4 3 2 1 1 1 1 1 1 1 1
1 1⁄2 1 1/2 Inch Schedule 40 82 59 37 21 15 9 8 7 5 4 3 3 2 1 1 1 1 1 1 1 1 1 1
1 1/2 Inch Schedule 80 70 51 32 18 13 8 7 6 4 3 3 2 1 1 1 1 1 1 1 1 1 1
2 2 Inch Schedule 40 135 99 62 36 26 16 13 11 8 7 6 5 4 3 3 2 1 1 1 1 1 1 1
2 Inch Schedule 80 118 86 54 31 22 14 12 10 7 6 5 4 3 3 2 1 1 1 1 1 1 1 1
2 1⁄2 2 1/2 Inch Schedule 40 193 141 89 51 37 22 19 16 12 10 8 7 6 4 4 3 3 2 1 1 1 1 1
2 1/2 Inch Schedule 80 170 124 78 45 32 20 17 14 10 9 7 6 5 4 3 3 3 2 1 1 1 1 1
3 3 Inch Schedule 40 299 218 137 79 57 35 30 25 18 15 13 11 9 7 6 5 5 4 3 3 2 2 2
3 Inch Schedule 80 265 193 122 70 51 31 26 22 16 14 11 9 8 6 5 5 4 3 3 2 2 2 1
3 1⁄2 3 1/2 Inch Schedule 40 401 293 184 106 77 47 40 33 25 21 17 14 12 10 8 7 6 5 4 4 3 3 3
3 1/2 Inch Schedule 80 358 261 164 95 68 42 35 30 22 18 15 13 10 8 7 6 6 5 4 3 3 3 3
4 4 Inch Schedule 40 517 377 238 137 99 61 51 43 32 27 22 18 15 12 11 9 8 7 5 5 4 4 4
4 Inch Schedule 80 464 338 213 123 89 54 46 39 29 24 20 17 14 11 9 8 7 6 5 4 4 4 3
5 5 Inch Schedule 40 815 594 374 216 156 96 81 68 50 42 35 29 24 20 17 15 13 11 9 8 7 7 6
5 Inch Schedule 80 736 537 338 195 141 86 73 61 45 38 32 26 22 18 15 13 12 10 8 7 7 6 6
6 6 Inch Schedule 40 * 859 541 312 225 138 117 98 73 61 51 42 35 28 24 21 19 16 13 11 11 10 9
6 Inch Schedule 80 * 770 485 279 202 124 105 88 65 55 46 38 31 25 22 19 17 14 12 10 9 9 8

*Please refer the NEC® for exact calculation.

Find the PVC Conduit Fill Chart for your Wire Size

To jump to the section of the PVC Conduit Fill Chart for your gauge of wire, select a wire size.

AWG Wire Size


MCM Wire Size


Conduit
Trade Size
in Inches
AWG Wire Conductor Size
14 12 10
1⁄2 1/2 Inch Schedule 40 11 8 5
1/2 Inch Schedule 80 9 6 4
3/4 3/4 Inch Schedule 40 21 15 9
3/4 Inch Schedule 80 17 12 7
1 1 Inch Schedule 40 34 25 15
1 Inch Schedule 80 28 20 13
1 1⁄4 1 1/4 Inch Schedule 40 60 43 27
1 1/4 Inch Schedule 80 51 37 23
1 1⁄2 1 1/2 Inch Schedule 40 82 59 37
1 1/2 Inch Schedule 80 70 51 32
2 2 Inch Schedule 40 135 99 62
2 Inch Schedule 80 118 86 54
2 1⁄2 2 1/2 Inch Schedule 40 193 141 89
2 1/2 Inch Schedule 80 170 124 78
3 3 Inch Schedule 40 299 218 137
3 Inch Schedule 80 265 193 122
3 1⁄2 3 1/2 Inch Schedule 40 401 293 184
3 1/2 Inch Schedule 80 358 261 164
4 4 Inch Schedule 40 517 377 238
4 Inch Schedule 80 464 338 213
5 5 Inch Schedule 40 815 594 374
5 Inch Schedule 80 736 537 338
6 6 Inch Schedule 40 * 859 541
6 Inch Schedule 80 * 770 485

*Please refer the NEC® for exact calculation.


Conduit
Trade Size
in Inches
AWG Wire Conductor Size
8 6 4
1⁄2 1/2 Inch Schedule 40 3 1 1
1/2 Inch Schedule 80 2 1 1
3⁄4 3/4 Inch Schedule 40 5 4 2
3/4 Inch Schedule 80 4 3 1
1 1 Inch Schedule 40 9 6 4
1 Inch Schedule 80 7 5 3
1 1⁄4 1 1/4 Inch Schedule 40 16 11 7
1 1/4 Inch Schedule 80 13 9 6
1 1⁄2 1 1/2 Inch Schedule 40 21 15 9
1 1/2 Inch Schedule 80 18 13 8
2 2 Inch Schedule 40 36 26 16
2 Inch Schedule 80 31 22 14
2 1⁄2 2 1/2 Inch Schedule 40 51 37 22
2 1/2 Inch Schedule 80 45 32 20
3 3 Inch Schedule 40 79 57 35
3 Inch Schedule 80 70 51 31
3 1⁄2 3 1/2 Inch Schedule 40 106 77 47
3 1/2 Inch Schedule 80 95 68 42
4 4 Inch Schedule 40 137 99 61
4 Inch Schedule 80 123 89 54
5 5 Inch Schedule 40 216 156 96
5 Inch Schedule 80 195 141 86
6 6 Inch Schedule 40 312 225 138
6 Inch Schedule 80 279 202 124

Conduit
Trade Size
in Inches
AWG Wire Conductor Size
3 2 1
1⁄2 1/2 Inch Schedule 40 1 1 1
1/2 Inch Schedule 80 1 1
3⁄4 3/4 Inch Schedule 40 1 1 1
3/4 Inch Schedule 80 1 1 1
1 1 Inch Schedule 40 3 3 1
1 Inch Schedule 80 3 2 1
1 1⁄4 1 1/4 Inch Schedule 40 6 5 3
1 1/4 Inch Schedule 80 5 4 3
1 1⁄2 1 1/2 Inch Schedule 40 8 7 5
1 1/2 Inch Schedule 80 7 6 4
2 2 Inch Schedule 40 13 11 8
2 Inch Schedule 80 12 10 7
2 1⁄2 2 1/2 Inch Schedule 40 19 16 12
2 1/2 Inch Schedule 80 17 14 10
3 3 Inch Schedule 40 30 25 18
3 Inch Schedule 80 26 22 16
3 1⁄2 3 1/2 Inch Schedule 40 40 33 25
3 1/2 Inch Schedule 80 35 30 22
4 4 Inch Schedule 40 51 43 32
4 Inch Schedule 80 46 39 29
5 5 Inch Schedule 40 81 68 50
5 Inch Schedule 80 73 61 45
6 6 Inch Schedule 40 117 98 73
6 Inch Schedule 80 105 88 65

Conduit
Trade Size
in Inches
AWG Wire Conductor Size
1/0 2/0 3/0
1⁄2 1/2 Inch Schedule 40 1
1/2 Inch Schedule 80
3⁄4 3/4 Inch Schedule 40 1 1 1
3/4 Inch Schedule 80 1 1 1
1 1 Inch Schedule 40 1 1 1
1 Inch Schedule 80 1 1 1
1 1⁄4 1 1/4 Inch Schedule 40 3 2 1
1 1/4 Inch Schedule 80 2 1 1
1 1⁄2 1 1/2 Inch Schedule 40 4 3 3
1 1/2 Inch Schedule 80 3 3 2
2 2 Inch Schedule 40 7 6 5
2 Inch Schedule 80 6 5 4
2 1⁄2 2 1/2 Inch Schedule 40 10 8 7
2 1/2 Inch Schedule 80 9 7 6
3 3 Inch Schedule 40 15 13 11
3 Inch Schedule 80 14 11 9
3 1⁄2 3 1/2 Inch Schedule 40 21 17 14
3 1/2 Inch Schedule 80 18 15 13
4 4 Inch Schedule 40 27 22 18
4 Inch Schedule 80 24 20 17
5 5 Inch Schedule 40 42 35 29
5 Inch Schedule 80 38 32 26
6 6 Inch Schedule 40 61 51 42
6 Inch Schedule 80 55 46 38

Conduit
Trade Size
in Inches
Wire Conductor Size
AWG MCM
4/0 250 300
1⁄2 1/2 Inch Schedule 40
1/2 Inch Schedule 80
3⁄4 3/4 Inch Schedule 40 1
3/4 Inch Schedule 80
1 1 Inch Schedule 40 1 1 1
1 Inch Schedule 80 1 1
1 1⁄4 1 1/4 Inch Schedule 40 1 1 1
1 1/4 Inch Schedule 80 1 1 1
1 1⁄2 1 1/2 Inch Schedule 40 2 1 1
1 1/2 Inch Schedule 80 1 1 1
2 2 Inch Schedule 40 4 3 3
2 Inch Schedule 80 3 3 2
2 1⁄2 2 1/2 Inch Schedule 40 6 4 4
2 1/2 Inch Schedule 80 5 4 3
3 3 Inch Schedule 40 9 7 6
3 Inch Schedule 80 8 6 5
3 1⁄2 3 1/2 Inch Schedule 40 12 10 8
3 1/2 Inch Schedule 80 10 8 7
4 4 Inch Schedule 40 15 12 11
4 Inch Schedule 80 14 11 9
5 5 Inch Schedule 40 24 20 17
5 Inch Schedule 80 22 18 15
6 6 Inch Schedule 40 35 28 24
6 Inch Schedule 80 31 25 22

Conduit
Trade Size
in Inches
MCM Wire Conductor Size (kcmil)
350 400 500
1⁄2 1/2 Inch Schedule 40
1/2 Inch Schedule 80
3⁄4 3/4 Inch Schedule 40
3/4 Inch Schedule 80
1 1 Inch Schedule 40 1
1 Inch Schedule 80
1 1⁄4 1 1/4 Inch Schedule 40 1 1 1
1 1/4 Inch Schedule 80 1 1 1
1 1⁄2 1 1/2 Inch Schedule 40 1 1 1
1 1/2 Inch Schedule 80 1 1 1
2 2 Inch Schedule 40 2 1 1
2 Inch Schedule 80 1 1 1
2 1⁄2 2 1/2 Inch Schedule 40 3 3 2
2 1/2 Inch Schedule 80 3 3 2
3 3 Inch Schedule 40 5 5 4
3 Inch Schedule 80 5 4 3
3 1⁄2 3 1/2 Inch Schedule 40 7 6 5
3 1/2 Inch Schedule 80 6 6 5
4 4 Inch Schedule 40 9 8 7
4 Inch Schedule 80 8 7 6
5 5 Inch Schedule 40 15 13 11
5 Inch Schedule 80 13 12 10
6 6 Inch Schedule 40 21 19 16
6 Inch Schedule 80 19 17 14

Conduit
Trade Size
in Inches
MCM Wire Conductor Size (kcmil)
600 700 750
1⁄2 1/2 Inch Schedule 40
1/2 Inch Schedule 80
3⁄4 3/4 Inch Schedule 40
3/4 Inch Schedule 80
1 1 Inch Schedule 40
1 Inch Schedule 80
1 1⁄4 1 1/4 Inch Schedule 40 1
1 1/4 Inch Schedule 80
1 1⁄2 1 1/2 Inch Schedule 40 1 1 1
1 1/2 Inch Schedule 80 1 1 1
2 2 Inch Schedule 40 1 1 1
2 Inch Schedule 80 1 1 1
2 1⁄2 2 1/2 Inch Schedule 40 1 1 1
2 1/2 Inch Schedule 80 1 1 1
3 3 Inch Schedule 40 3 3 2
3 Inch Schedule 80 3 2 2
3 1⁄2 3 1/2 Inch Schedule 40 4 4 3
3 1/2 Inch Schedule 80 4 3 3
4 4 Inch Schedule 40 5 5 4
4 Inch Schedule 80 5 4 4
5 5 Inch Schedule 40 9 8 7
5 Inch Schedule 80 8 7 7
6 6 Inch Schedule 40 13 11 11
6 Inch Schedule 80 12 10 9

Conduit
Trade Size
in Inches
MCM Wire Conductor Size (kcmil)
800 900 1000
1⁄2 1/2 Inch Schedule 40
1/2 Inch Schedule 80
3⁄4 3/4 Inch Schedule 40
3/4 Inch Schedule 80
1 1 Inch Schedule 40
1 Inch Schedule 80
1 1⁄4 1 1/4 Inch Schedule 40
1 1/4 Inch Schedule 80
1 1⁄2 1 1/2 Inch Schedule 40 1 1
1 1/2 Inch Schedule 80 1
2 2 Inch Schedule 40 1 1 1
2 Inch Schedule 80 1 1 1
2 1⁄2 2 1/2 Inch Schedule 40 1 1 1
2 1/2 Inch Schedule 80 1 1 1
3 3 Inch Schedule 40 2 2 1
3 Inch Schedule 80 2 1 1
3 1⁄2 3 1/2 Inch Schedule 40 3 3 3
3 1/2 Inch Schedule 80 3 3 2
4 4 Inch Schedule 40 4 4 3
4 Inch Schedule 80 4 3 3
5 5 Inch Schedule 40 7 6 6
5 Inch Schedule 80 6 6 5
6 6 Inch Schedule 40 10 9 8
6 Inch Schedule 80 9 8 7


Above information referenced from Table C.10, and Table C.11 in the National Electric Code (NEC®) of 2020

For more information on the following types of conduit, please see the tables listed below in the Appendix C of the National Electric Code® of 2020.

Electrical Metal Tubing (EMT) -- Table C.1 or our Conduit Fill Chart for EMT

Electrical Non-Metallic Tubing (ENT) -- Table C.2

Flexible Metallic Conduit -- Table C.3 or our Conduit Fill Chart for Flexible Metal Conduit

Intermediate Metal Conduit (IMC) -- Table C.4 or our Conduit Fill Chart for IMC

Liquidtight Flexible Non-Metallic Conduit (Type LFNC-A) -- Table C.5

Liquidtight Flexible Non-Metallic Conduit (Type LFNC-B) -- Table C.6

Liquidtight Flexible Non-Metallic Conduit (Type LFNC-C) -- Table C.7

Liquidtight Flexible Metallic Conduit (LFMC) -- Table C.8

Rigid Metallic Conduit -- Table C.9 or our Conduit Fill Chart for Rigid Metal Conduit

Rigid PVC Conduit, Schedule 80 -- Table C.10

Rigid PVC Conduit, Schedule 40 -- Table C.11

Type A PVC Conduit -- Table C.12

Type EB PVC Conduit -- Table C.13

If you have any other questions, see the NEC® Code Book or ask an Elliott Electric Salesperson.


Shop Related Products

Schedule 40
PVC Conduit

PCV conduit schedule 40

Shop Schedule 40 Conduit

Schedule 80
PVC Conduit

PCV conduit schedule 80

Shop Schedule 80 Conduit

PVC Fittings
and Accessories

PCV conduit Fittings and Accessories

Shop Fittings and Accessories

Metallic Conduit

metallic emt conduit

Shop Metallic Conduit

Liquid Tight Conduit

Nonmetallic Liquid-Tight Conduit, HVAC Equipment

Shop Liquid Tight Conduit

Building Wire and Cable

Romex non-metallic-sheathed-cable

Shop Wire and Cable

Warning: When using this information to perform electrical work, call a licensed electrician and consult the NEC® for safety. All licensed electricians have passed examinations covering the National Electric Code®, know state and local building codes, and may carry insurance to cover damages.