To calculate the maximum current in an insulated wire when there are more than 3 current carrying wire conductors in the same raceway or cable, first, find the
maximum allowable current
for a raceway or cable with less than 3 current carrying wire conductors, then multiply that maximum current by the percentage number from the
Adjustment Factors for More Than 3 Current Carrying Conductors Chart below and divide by 100.
Maximum Current Adjustment Factors
for More Than 3 Current‑Carrying Conductors
in a Raceway or Cable
Number of Conductors in a Raceway |
Percent of Total Value |
4 – 6 |
80 |
7 – 9 |
70 |
10 – 20 |
50 |
21 – 30 |
45 |
31 – 40 |
40 |
41 or Above |
35 |
Table 310.15(C)(1), 2020 NEC®