UL Fuse Class Chart - Types of Fuses and Fuse Size
Need help choosing a fuse from the many sizes and types of fuses? Use these fuse charts to find the best fuse type given your required fuse overload characteristics, interrupting rating amps, AC voltage rating,
and available amps fuse rating.
Select a UL fuse class to see fuse characteristics and vendor information for that UL class of fuses.
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600* |
Available Amp Rating |
200 ‑ 6000 |
601 ‑ 4000 |
200 ‑ 2000 |
Littelfuse |
KLPC
|
KLLU
|
LDC
|
Bussman |
KRPC
|
KLU
|
n/a |
Edison |
n/a |
LCL
|
n/a |
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600* |
Available Amp Rating |
200 ‑ 6000 |
601 ‑ 4000 |
Littelfuse |
KLPC
|
KLLU
|
Bussman |
KRPC
|
KLU
|
Edison |
n/a |
LCL
|
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600* |
Available Amp Rating |
200 ‑ 2000 |
Littelfuse |
LDC
|
Bussman |
n/a |
Edison |
n/a |
* LDC rated 600 volts AC/DC
Fuse Overload Characteristics: |
Time Delay |
Fast Acting |
Interrupting Rating Amps: |
200,000 |
200,000 |
AC Voltage Rating: |
250 |
600 |
250 |
600 |
Available Amp Rating |
1/10 ‑ 600 |
1/10 ‑ 600 |
1 ‑ 600 |
1 ‑ 600 |
Littelfuse |
LLNRK
|
LLSRK
|
KLNR
|
KLSR
|
Bussman |
LPNRK
|
LPSRK
|
KTNR
|
KTSR
|
Edison |
LENRK
|
LLSRK
|
NCLR
|
SCLR
|
Fuse Overload Characteristics: |
Time Delay |
Interrupting Rating Amps: |
200,000 |
AC Voltage Rating: |
250 |
600 |
Available Amp Rating |
1/10 ‑ 600 |
1/10 ‑ 600 |
Littelfuse |
LLNRK
|
LLSRK
|
Bussman |
LPNRK
|
LPSRK
|
Edison |
LENRK
|
LLSRK
|
Fuse Overload Characteristics: |
Fast Acting |
Interrupting Rating Amps: |
200,000 |
AC Voltage Rating: |
250 |
600 |
Available Amp Rating |
1 ‑ 600 |
1 ‑ 600 |
Littelfuse |
KLNR
|
KLSR
|
Bussman |
KTNR
|
KTSR
|
Edison |
NCLR
|
SCLR
|
*** RK1 Class fuses are Ultra Fast Clearing
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
250 |
Available Amp Rating |
35 ‑ 600 |
1/10 ‑ 600 |
Littelfuse |
FLNR‑ID
|
FLNR
|
Bussman |
FRNR
|
FRNR
|
Edison |
ECNR
|
ECNR
|
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600 |
Available Amp Rating |
1/10 ‑ 600 |
Littelfuse |
FLSR & FLSR‑ID,
IDSR
|
Bussman |
FRSR
|
Edison |
ECSR
|
Fuse Overload Characteristics |
Fast Acting |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating: |
300** |
600 |
Available Amp Rating |
1 ‑ 1200 |
1 ‑ 1200 |
Littelfuse |
JLLN**
|
JLLS
|
Bussman |
JJN
|
JJS
|
Edison |
TJN
|
TJS
|
** JLLN Class T Fuse is UL Listed at 300 volts
Fuse Overload Characteristics |
Time Delay |
Fast Acting |
Interrupting Rating Amps |
200,000 |
200,000 |
AC Voltage Rating |
600 |
600 |
Available Amp Rating |
8/10 ‑ 600 |
1 ‑ 600 |
Littelfuse |
JTD & JTD‑ID
|
JLS
|
Bussman |
LPJ
|
JKS
|
Edison |
JDL
|
JFL
|
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600 |
Available Amp Rating |
8/10 ‑ 600 |
Littelfuse |
JTD & JTD‑ID
|
Bussman |
LPJ
|
Edison |
JDL
|
Fuse Overload Characteristics |
Fast Acting |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600 |
Available Amp Rating |
1 ‑ 600 |
Littelfuse |
JLS
|
Bussman |
JKS
|
Edison |
JFL
|
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600 |
Available Amp Rating |
1/10 ‑ 30 |
2/10 ‑ 30 |
Littelfuse |
KLDR
|
CCMR (formerly KLMR)
|
Bussman |
FNQR
|
LPCC
|
Edison |
HCTR
|
EDCC
|
Fuse Overload Characteristics |
Fast Acting |
Interrupting Rating Amps |
200,000 |
AC Voltage Rating |
600 |
Available Amp Rating |
1/10 ‑ 30 |
Littelfuse |
KLKR
|
Bussman |
KTKR
|
Edison |
HCLR
|
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps: |
200,000 |
AC Voltage Rating |
600 |
Available Amp Rating |
35 ‑ 60 |
Littelfuse |
CCMR
|
Bussman |
LPCC
|
Edison |
EDCC
|
Fuse Overload Characteristics |
Time Delay |
Interrupting Rating Amps |
100,000 |
AC Voltage Rating |
480* |
Available Amp Rating |
1/2 ‑ 60 |
Littelfuse |
SLC
|
Bussman |
SC
|
Edison |
SEC
|
* LDC rated 600 volts AC/DC
Fuse Overload Characteristics |
Fast Acting |
Interrupting Rating Amps |
50,000 |
AC Voltage Rating |
250 |
600 |
Available Amp Rating |
1 ‑ 600 |
1 ‑ 600 |
Littelfuse |
NLN
|
NLS
|
Bussman |
NON
|
NOS
|
Edison |
KON
|
KOS
|
Fuse Overload Characteristics |
Renewable Fuses Fast Action |
Interrupting Rating Amps |
10,000 |
AC Voltage Rating |
250 |
600 |
Available Amp Rating |
1 ‑ 600 |
1 ‑ 600 |
Littelfuse |
RLN
|
RLS
|
Bussman |
REN
|
RES
|
Edison |
ERN
|
ERS
|
* LDC rated 600 volts AC/DC
** JLLN Class T fuse is UL Listed at 300 volts
*** Class RK1 fuse is Ultra Fast Clearing
Warning: When using this information to perform electrical work, call a licensed electrician and consult the NEC® for safety.
All licensed electricians have passed examinations covering the National Electric Code®, know state and local building codes,
and may carry insurance to cover damages.